The 57,000m3/hr Thermo Air AHU was designed and manufactured to meet the minimum cleanroom ISO 8 grade of air quality. The units consisted of 2no high efficiency DIDW backward curved centrifugal fans c/w IE3 motors. Heat reclamation was achieved via the 3 way mixing section and filtered though banks of G4, F7, and F9 filters. Cooling was achieved via the 350kW chilled water coil. the AHU was delivered in sections to assist install and transport, with the overall unit dimensions at 11.86m x 3.2m x 3.1m (L x W x H).
Client: Athlone based pharmaceutical / manufacturing company
M&E Contractor: Calcool Engineering
Services: 16m3/s Supply and Extract AHU built to L1 / D1 / TB2 / T1 standard
Year: 2017